COMPANY NEWS
Hall Current Sensor EHR1000
Product Introduction:
Hall Current Sensor EHR1000
For the electronic measurement of currents:DC,AC,pulsed,mixed,
with a galvanic isolation between the primary(high power)
circuit and the secondary(electronic) circuit.
● Operating performance ( AT =25℃ )
Primary nominal r.m.s. current 0~1000 A
Primary current measuring range :0~±1000A
Output voltage : ±4 V
Supply voltage : ±15( ±5% ) V
Current consumption : <25 mA
Linearity : ≦±0.5 @0...±IPN %
Accuracy :@IPN,VC=±15V,TA=25℃, X ±1 %
Offset voltage :@IP=0,TA=25℃ VO <±10 mV
Thermal drift of VO : ≦±1 mV/℃
Thermal drift of VOUT : ≦±0.05 %/℃
Response time : <3 @90% of Ip µs
di/dt accurately followed : 50 A/μs
Hysteresis offset current : ≦±10 @±3IPN→0 mV
Isolation voltage : 3 @50(60)Hz/1min KV
Isolation resistance : 500 MΩ
Frequency bandwidth : 0~50 KHz
● General data
Operating temperature : -40~+85 ℃
Storage temperature : -45~+100 ℃
Mass :230 g